One time testing cannot be based to a big decision towards
any action on transformer. So periodic testing is Invariably
required to monitor the trend in a test results and action
can be initiated following the trend. If a Single transformer
is saved due to action taken after monitoring the trend
in result. It’s a big asset to the organization and
on the other hand a huge data on different transformer is
gathered on which future action can be based.
All the oil testing parameters can be used for trending
purpose, but Dissolved Gas Analysis is the best tool which
can be used for Trending, Monitoring and early fault detection
purpose.
Information from the analysis of gasses dissolved in insulating
oils is valuable in a preventative maintenance program.
A number of samples must be taken over a period of time
for developing trends. Data from DGA can:
| - |
Provide advance warning of
developing faults |
| - |
Provide a means for conveniently scheduling repairs
|
| - |
Monitor the rate of fault development |
DGA reports have a diagnostic section where an analysis
is performed on the dissolved gas results using IS:10593
(Ratio Method) & Roger Method. The information provided
by the report is often sufficient to properly evaluate the
operating status of the transformer but gassing history
is also an extremely important aspect of fault detection.
At NDL, all DGA results are kept in a readily accessible
database and historical data is checked every time a sample
is analyzed. When a significant change in gas concentrations
is observed, the client is contacted immediately. through
Telephone, fax or e-mail.
At NDL Automation of Testing & Reporting led to better
management of transformer oil tests. Re sampling schedule,
gas history graphs and fault assessment algorithms based
on stored DGA results are provided to offer a quick and
simple way of deciding which transformers should be tested
and in which priority.
