Home | Contact Us | Sitemap
About Us|Products & Services|Strengths|Clients|Safety Solutions
Sensofast
Transformer Safety Management Services
Fault Prediction
Clients
  total transformer care solutions
  fault prediction
  trending and monitoring
  residual life assesment
  electrical testing
  oil testing
maintenance
  high vacuum filtration
  sensofast
  analyst software
  AMC packages
Maintenance
Predictive Maintenanc
Off line: Dissolved Gas Analysis (DGA)
Electrical Faults
- Arcing
- Sparking
- Corona
- Partial discharge

Thermal Faults
- Over heating
- Hot Spot
- Hot Metal
Trending & Monitoring of key parameter DGA & oil analysis
On Line Evolved Hydrogen (Key fault Gas) monitoring by Sensofast™
- Analyst™ software On site monitoring of key parameters. OTI, WTI, LOAD Evolved Hydrogen Sensofast™
Ageing
- Furan Analysis in oil
- De Polymerization of paper in oil

Preventive Maintenance
Transformer’s life mainly based on insulation
- Oil Quality IS : 1866
- Core & Winding Improvement of IR value
- High vacuum filtration Improvement of IR value
- Bushing Tan delta & Capacitance
- Overt hauling Life & Power loss improvement
- Protection System Testing & Calibration


Breakdown Maintenance
NDL believes in providing Zero breakdown
- By Regular online trend monitoring
- By key predict & preventive action

Schedule for diagnostic, condition monitoring & life assessment of transformers
For Predictive Maintenance:-

Test On Tests References Recommended for Key & Critical Transformer Recommended for General Purpose Transformers
Transformer Oil Breakdown Voltage IS 1866 6 monthly Yearly
  Water Contents IS 1866 6 monthly Yearly
  Tan Delta IS 1866 6 monthly Yearly
  Resistively IS 1866 6 monthly Yearly
  Flash Point IS 1866 6 monthly Yearly
  Inter Facial Tension IS 1866 6 monthly Yearly
  Neutralization Value IS 1866 6 monthly Yearly
  Sediments and Sledge IS 1866 6 monthly Yearly
  Dissolved Gas Analysis IS 10593 3 monthly 6 monthly
         
Transformer Insulation Paper DP Of Paper IEC 450 5 Yearly after 15 years of age. 5 Yearly after 15 years of age.
         
Transformer Solid Insulation Furan Analysis IEC 1198 Yearly after 15 years of age 2 Yearly after 15 years of age
  Insulation Resistance   Yearly 2 Yearly
  Polarization Index   Yearly 2 Yearly
  Capacitance & Tan Delta Tests   Yearly 2 Yearly
  Leakage Current Test   Yearly 2 Yearly
         
Conductor & Tap Changer DC Winding Resistance   Yearly 2 Yearly
  Ratio Test & Phase Angle Error Tests   Yearly 2 Yearly
  Knee Point Voltage Tests   Yearly 2 Yearly
         
Core Excitation Current Tests   Yearly 2 Yearly
  Magnetic Current Test   Yearly 2 Yearly
         
HV Bushing Capacitance & Tan Delta Tests   Yearly 2 Yearly
         

Preventive Maintenance
Test on Tests References Recommended. for Key & Critical Transformer Recommended for General Purpose Transformers
Transformer I.R Value Improvement (High Vacuum Filtration) IS 10028 Yearly Yearly
  Filtration IS 10028 Yearly Yearly
  Reclamation IS 10028 Based on Oil Test Based on Oil Test
  Overhauling IS 10028 5 Yearly 7 Yearly

 