| Test On |
Tests |
References |
Recommended for Key & Critical
Transformer |
Recommended for General Purpose
Transformers |
| Transformer Oil |
Breakdown Voltage |
IS 1866 |
6 monthly |
Yearly |
| |
Water Contents |
IS 1866 |
6 monthly |
Yearly |
| |
Tan Delta |
IS 1866 |
6 monthly |
Yearly |
| |
Resistively |
IS 1866 |
6 monthly |
Yearly |
| |
Flash Point |
IS 1866 |
6 monthly |
Yearly |
| |
Inter Facial Tension |
IS 1866 |
6 monthly |
Yearly |
| |
Neutralization Value |
IS 1866 |
6 monthly |
Yearly |
| |
Sediments and Sledge |
IS 1866 |
6 monthly |
Yearly |
| |
Dissolved Gas Analysis |
IS 10593 |
3 monthly |
6 monthly |
| |
|
|
|
|
| Transformer Insulation Paper |
DP Of Paper |
IEC 450 |
5 Yearly after 15 years of age. |
5 Yearly after 15 years of age. |
| |
|
|
|
|
| Transformer Solid Insulation |
Furan Analysis |
IEC 1198 |
Yearly after 15 years of age |
2 Yearly after 15 years of age |
| |
Insulation Resistance |
|
Yearly |
2 Yearly |
| |
Polarization Index |
|
Yearly |
2 Yearly |
| |
Capacitance & Tan Delta Tests |
|
Yearly |
2 Yearly |
| |
Leakage Current Test |
|
Yearly |
2 Yearly |
| |
|
|
|
|
| Conductor & Tap Changer |
DC Winding Resistance |
|
Yearly |
2 Yearly |
| |
Ratio Test & Phase Angle Error Tests |
|
Yearly |
2 Yearly |
| |
Knee Point Voltage Tests |
|
Yearly |
2 Yearly |
| |
|
|
|
|
| Core |
Excitation Current Tests |
|
Yearly |
2 Yearly |
| |
Magnetic Current Test |
|
Yearly |
2 Yearly |
| |
|
|
|
|
| HV Bushing |
Capacitance & Tan Delta Tests |
|
Yearly |
2 Yearly |
| |
|
|
|
|